Leave Your Message

China VD4 Medium-Voltage Indoor Vacuum Circuit Breaker Suppliers | Reliable Factory Solutions

Introducing the VD4 Series, a high-performance solution for your electrical needs, designed by trusted China suppliers and manufactured in our advanced factory. This model is rated for voltages ranging from 2.5 to 34.5kV, making it suitable for various applications, both outdoor and indoor. Complying with the international standard IEC 60694, the VD4 Series ensures reliability and safety in your electrical systems. With a two-year warranty, you can be confident in the longevity and quality of your investment. Choose the VD4 Series for dependable electrical solutions from a leading manufacturer in China

    This circuit breaker is made with mature APG technology. The application of VB4P terminal buffer guarantees the indoor terminal is ever more reliable in nay operation environment. VB4P can fully meet the requirement of GB, DL, IEC, DIN, VDE as well as standards of other advanced industrial countries.

    General IconGeneral

    VB4P medium-voltage indoor vacuum circuit breaker is applicable for three-phase AC power system of rated voltage up to 12~24kV and frequency 50/60Hz,widely used in many fields such as power plant, transformer substation, petrol chemical industry, metallurgy, manufacturing industry, airport, residential area, etc., to control and protect the electric equipment, especially, It is used for the occasion that needs infrequent operation at rated current or multi-breaking short circuit current, may be mounted in the indoor air insulating switchgear like type KYN28 or AMS, ABB type ZS1 series, etc. This circuit breaker is standards as GB1984-2003 AC high voltage circuit breaker,JB3855 3.6-40.5Kv indoor AC High voltage circuit breaker,DL/T403 Specification of 12-40.5Kv indoor High voltage vacuum circuit breaker for order as well as IEC60694.

    Service environment IconService environment

    Air temperature: Maximum temperature: +40℃; Minimum temperature:-25℃.
    Humidity: Monthly average humidity 95%; Daily average humidity 90% .
    Altitude above sea level: Maximum installation altitude: 2500m.
    Ambient air not apparently polluted by corrosive and flammable gas, vapor etc.
    No frequent violent shake.

    3D Mechanism Icon3D Mechanism introduction

    VB4P Medium-Voltage Indoor Vacuum Circuit Breaker 3D Mechanism

    Innovative Design IconInnovative product design

    Damper with perfect performance
    Thanks to the refined damper with perfect performance and the new cam gear with curvilinear design, the contacts rebounding value during the breaker opening is reduced more and the breaker can be opened reliably. Besides, the bellows in vacuum interrupter are avoided to be broken down due to contacts over bounding and also the mechanical lifetime of operating mechanism is ensured.
    Special design of repair without many tools
    During the design for VB4P circuit-breaker, the installation and repair must be taken into account. So for the disassembly of parts or accessories, users need no special tools and the repair becomes more convenient. Besides, all of the secondary controlling components are in front of the operating mechanism, which also make maintenance and repair convenient.
    Modularized operating mechanism
    Modularized operating mechanism is another feature of VB4P. It can be divided into closing module, opening module, mainaxis module and secondary wiring module, which make the mechanism have characteristic of standard manufacture method, short producing period, convenient maintenance and rapid replacing. These modules are standard and applicable to all VB4P so the costs of facilities management and maintenance are reduced.
    Self- lubricative bearing without oil
    Self-lubricative bearing without oil used for VB4P circuit-breaker is very applicable to over-load and low-speed conditions and avoids the lost-lubricative phenomena due to oil-lubricative bearing out of work for a long time. The free-maintenance can be realized accordingly.
    Conductors with silvered surface
    All the conductors of VB4P circuit-breaker are disposed by silvered process so that it do not only reduce the contacting resistance but also improve the electricity-conducting capacity of conductors. Thanks to the reduced resistance the heat from circuit-breaker running can be decreased and the breaker’s lifetime is also lengthened.
    Single closing spring device

    Single closing spring device

    Self-lubricative Bearing

    Self- lubricative Bearing without Oil

    Silvered Conductors

    Conductors with Silvered Surface

    Embedded Pole IconEmbeded pole design

    ● High Reliability
    ● Free Maintenance
    ● Stable Insulating Property
    ● Firm Structure
    ● Miniaturization
    ● More Environmental Protection
    Embeded pole design

    Vacuum Interrupter IconVacuum Interrupter with Excellent Performance

    Unique R-shaped Contact Terminal Design
    Complete One-Time Sea-Exhaust Technology
    High & Stable Quality Ceramic Metallization Technology
    Stainless Steel Direct Rivet Weld Technology
    Vacuum Interrupter

    Installation IconInstallation size

    Installation size diagram
    Frequently Asked Questions (FAQ)
    What is the rated voltage for the VB4P circuit breaker?
    The VB4P medium-voltage indoor vacuum circuit breaker is designed for three-phase AC power systems with a rated voltage of up to 12~24kV.
    What are the ambient temperature requirements for operation?
    The device operates reliably within a temperature range of -25°C to +40°C.
    Does the operating mechanism require frequent oiling?
    No, the VB4P uses self-lubricative bearings without oil, which are designed for maintenance-free operation and prevent failure due to dried-out lubricants.
    What standards does this circuit breaker comply with?
    It meets international and national standards including IEC60694, GB1984-2003, JB3855, and DL/T403.
    What is the benefit of the silvered surface on conductors?
    Silvered conductors reduce contacting resistance, improve electricity-conducting capacity, and decrease heat generation, thereby extending the breaker's lifetime.
    At what altitude can the VB4P be installed?
    The maximum recommended installation altitude for the VB4P circuit breaker is 2500 meters above sea level.

    Leave Your Message