FAR Series 15KV/27KV/38KV Auto Circuit Recloser - Reliable China Suppliers & Factory Solutions
General
Farady Electric strives to bring our customers the latest technology, competitive pricing, and the best service for pole-mounted Auto circuit reclosers.
The FAR series Auto circuit recloser can be used on overhead distribution lines as well as distribution substation applications for all voltage classes from 11kV up to 38kV in 50/60Hz power systems, with a rated current reaching up to 1600A.
Service Condition
- A Air temperature: Maximum temperature: +85℃; Minimum temperature: -45℃.
- B Humidity: Monthly average humidity 95%; Daily average humidity 90%.
- C Altitude above sea level: Maximum installation altitude: 2500m or higher.
- D Ambient air not apparently polluted by corrosive and flammable gas, vapor, etc.
- E No frequent violent shake.
Product Structure
| 1 | ON/OFF Indicator | 2 | Emergency Close | 3 | Counter |
| 4 | Manual OFF | 5 | Earthing | 6 | Secondary Socket |
| 7 | Magnet Mechanism |
- 1 High quality Solid Epoxy resin material
- 2 Fully comply with ANSI std
- 3 Guarantee 30,000 times operation, Environment friendly, Oil / SF6 Gas free
- 4 Suitable for both Pole mounted or Substation available
- 5 Reliable and Enhanced Life Expectancy
- 6 Ambient temp: -40℃~80℃
| 1 | Rogowski coil | 2 | Voltage Sensor | 3 | Vacuum Interrupter |
| 4 | CT | 5 | Conductor | 6 | Push Rod |
| 7 | Push Reed |
- 1 High quality Vacuum Interrupter
- 2 Voltage sensor Integrated
- 3 CT Integrated
- 4 Reliable Push rod
- 5 Minimized moving components
- 6 Maintenance free design
Controller
1.1 Description
1. Voltlogic-351 series recloser controller is a medium voltage overhead line grid monitoring unit. It can combine with vacuum circuit breakers to achieve automatic reclosing, measurement monitoring, fault analysis, and event records. It provides a safer power grid for cutting line faults, automatic recovery operation, and power automation.
2. The controller is suitable for outdoor switchgear applications up to 38kV, including vacuum circuit breakers, oil circuit breakers, and gas circuit breakers.
3. The controller integrates line protection, control, measurement, and monitoring of voltage and current signals for outdoor automated installations.
4. It serves as an automatic management unit for single way, multi-way, ring network, and dual-power sourcing, complete with all voltage and current signal functionalities.
5. The column switch intelligent controller supports: Wireless (GSM/GPRS/CDMA), Ethernet mode, WIFI, optical fiber, power line carrier, RS232/485, RJ45, and other forms of communication, with direct access to station premises equipment (such as TTU, FTU, DTU, etc.).
| Protection functions | ANSI code | Name in Device |
|---|---|---|
| Phase overcurrent | 50P | P.OC |
| Overload | 49 | Overload |
| Phase Time-Overcurrent | 51P | P.Curve |
| Ground Overcurrent | 50G/N | E.F |
| Recloser | 79 | Reclose |
| Phase overcurrent cold load pick-up | CLPU 50 | Cold Load |
| Switch-Onto-Fault | SOTF | |
| Undervoltage | 27 | Under volt |
| Overvoltage | 50P | P.OC |
- 1 Phase current IA, IB, IC RMS, Zero Sequence
- 2 Voltage Uab, Ubc, Uca, U0
- 3 Active power, reactive power and power factor
- 4 Frequency
| Circuit breaker control | 94 |
| Latching / acknowledgement | 86 |
- A Complete protection configuration; all protection functions can be switched on/off flexibly.
- B 6 channels signal input.
- C 4 channels current measure.
- D 4 channels voltage measure.
- E Large capacity flash memory records at least 100 historical events without data loss upon power outage.
- F Operating loop supports AC and DC, adaptive open/close brake function, co-working smoothly with various breakers.
- G Comprehensive self-inspection monitors working conditions in-service to ensure maximum equipment reliability.
- A Trip logs
- B SOE logs
- C Alarm logs
- 1 RS485, RS232 port, and Ethernet
- 2 Protocols: IEC60870-5-101, IEC60870-5-104, IEC61850, Modbus RTU, DNP3.0
User Interface
The operator interface is designed to provide a user-friendly method of controlling, viewing menus, entering settings, and retrieving data from the relay. Four buttons are provided for navigation around the menu structure.
Projects
Installation
Frequently Asked Questions (FAQ)
The FAR series Auto circuit recloser accommodates overhead lines and substation systems across voltage classes from 11kV up to 38kV (50/60Hz), with rated currents reaching up to 1600A.
The equipment fully satisfies both IEC62271 and ANSI/IEEE C37.60 standards for distribution circuit reclosers.
Constructed using high-quality solid epoxy resin, the unit is entirely Oil and SF6 gas-free. It features an eco-friendly design guaranteed for up to 30,000 maintenance-free operations.
It features RS232, RS485, and Ethernet ports, supporting protocols such as IEC60870-5-101, IEC60870-5-104, IEC61850, Modbus RTU, and DNP3.0, as well as wireless GSM/GPRS/CDMA and optical fiber connections.
The system operates reliably in temperatures ranging from -45℃ to +85℃ and at installation altitudes of 2500m or higher.
Yes, it incorporates high-capacity flash memory that preserves at least 100 historical trip, SOE, and alarm events with zero data loss during power failure.