KYN28 Series Withdrawable Metal Clad Switchgear - Reliable China Suppliers and Factory for 2.5-34.5kV Solutions
General
The switchgear meets IEC298, GB3906-91. In addition to be used with domestic VSI vacuum circuit breaker, it can also be used with VD4 from ABB, 3AH5 from Siemens domestic ZN65A, and VB2 from GE, etc., it is truly a power distribution device with good performance.
In order to meet the requirement for wall mounting and front-end maintenance, the switchgear is equipped with a special current transformer, so that the operator can maintain and inspect it in front of the cubicle.
Service Environment
Structure & Basic Components
Overall Size and Weight
| Item | With VS1, VD4 inside | With VS1, VD4 inside | With 3AH5, ZN65A |
|---|---|---|---|
| W×D×H(mm) | 650×1400×2200 | 800(1000)×1500×2200 | 800(1000)×1700×2200 |
| Weight (kg) | 700 | 800 | 900 |
When the rated current is more than 1600A, cubicle width shall be 1000 mm, and cubicle height will be 1660mm and for schema of rear overhead line in.
1) Width of cabinet: 650mm(compound insulation) or 800mm(air insulation) at current 2) Width of cabinet: 1000mm at current > 1250A;
3) Depth of cabinet: 1400mm (650mm width) for incoming/outgoing cables;
4) Depth of cabinet: 1500mm (800mm width) for incoming/outgoing cables;
5) Depth of cabinet: 1600mm for rear overhead incoming/outgoing cables.
| A | B | L1 | B1 | Reference weight (Kg) |
|---|---|---|---|---|
| 650 | 1400 | 380 | 315 | 700 |
| 800 | 1500 | 530 | 315 | 800 |
| 1600 overhead | 900 | |||
| 1000 | 1500 | 730 | 490 | 1100 |
| 1600 overhead | 1200 | |||
| 900 | 1700(with 3AH5) | 600 | 415 | 1000 |
Structure Features
Busbar compartment, circuit breaker compartment, cable compartment; low-voltage compartment.
Schematics of Dimensions
Main Components Characteristics
![]() |
VS1-12 indoor drawable vacuum circuit breaker. Rated voltage 12kV up to 24kV; Rated current 630A up to 4000A; Rated short circuit breaking current 20kA up to 40kA; Mechanical life 10,000 times. |
![]() |
VD4 embedded pole indoor vacuum circuit breaker. Rated voltage 12kV up to 24kV; Rated current 630A up to 4000A; Rated short circuit breaking current 20kA up to 40kA; Mechanical life 10,000 times. |
![]() |
VSM magnetic actuator indoor VCB. Rated voltage 12kV up to 24kV; Rated current 630A up to 4000A; Rated short circuit breaking current 20kA up to 40kA; Mechanical life 100,000 times. |
Transportation, Maintenance and Order
Transportation and Storage: The switch cabinet should be transported vertically. It should not be exposed outside for a long time and should be stored in a dry, ventilated indoor warehouse. Outer package validity is normally no more than 1 year.
Maintenance: Free of maintenance for 3 years under normal conditions. Maintenance periodicity is normally once every year. Key tasks include fastening electrical connectors, cleaning parts with a dust collector, and performing switching operations for all switches.
Order Requirements
Complete-set Product Documents: Qualification Certificate, Installation and Operation Instruction, Packing List, and Engineering Design Documents.
Required Information for Order:
- Wiring diagram of Main circuit Loop and Special Technical Requirements.
- Installation Arrangement Plan of switch panel.
- Specification of components inside and schematic diagrams of auxiliary/control loops.
- Other specially required written documents.